Appliances

Tag, make, model, and high-fire input. Several into a common: type each MBH here. The connector carries one. The common carries all.

MBH

What are you sizing

Draft is a boiler, water heater, or furnace chimney. Losses is a generator, engine, or combustion-air job.

Appliance

What are Categories I, II, III, IV?

Categories I – IV

Two questions: does the vent run under negative pressure (the chimney pulls) or positive pressure (the appliance pushes)? And is the appliance non-condensing or condensing?

CatPressureCondensingPick
INegative — the chimney pullsNon-condensing — gases stay above dew pointDraft hood, or UL 103 if there is no hood
IINegative — the chimney pullsCondensing — gases drop below dew pointUL 1738
IIIPositive — the appliance pushesNon-condensing — gases stay above dew pointUL 103
IVPositive — the appliance pushesCondensing — gases drop below dew pointUL 1738

Firing

Type what the appliance IOM or rating plate printed. We convert to the actual cfm the flue has to carry.

MBH

high-fire from the rating plate

°F

350°F unless the appliance IOM says otherwise

Burner / fuel

Fuel, excess air, CO₂, O₂. 15% excess air is the default — confirm with the appliance or burner manufacturer. Change one number and the others follow.

%

5.3% in the vent after dilution

%

from the analyzer, if you have it

M = 1.60 lb products / 1,000 Btu · hood dilution is already in M. Confirm burner excess air with the appliance manufacturer — do not type it here.

Ambient, barometer, F
°F

default 60°F

in Hg

auto 29.92

0.40 ≤18″ · 0.30 above

ft

ups only · appliance outlet to cap

ft

this size: include that rise + horizontals

H is the ups, outlet to cap. L is this diameter’s full centerline — that rise plus every horizontal and offset. Do not type only the horizontal.

in

Fittings

k on this Vh

Count what’s in this flue. Elbows are k, not extra length.

0.15
0.40
0.65
0.25
1.00
1.25
0.50

10″ down to 8″: leave this flue at 10″, tap that button, type 8″ on the new one. The reducer k shows up between them. Do not put it under Other k — that is the warning you saw. A boot tee on the 8″ is the takeoff instead of a reducer; count the boot tee on the 8″, not both.

ASHRAE, lumped: Dt from total vertical rise. Δp = Σ k × Vh. Tap a ? for how you use that box. Field guide